Typical Physical Characteristics Of Transformer Oil I
Test Method | Typical | |
---|---|---|
Appearance | A representative sample of the oil shall be examined in a 100 mm thick layer at 27ºC | Clear and transparent and free from suspended matter or sediments |
Density at 29.5ºC, g/cc | IS 1448 [P : 16] : 1990 | 0.8279 |
Kinematic viscosity, | IS 1448 [P : 25] : 1976 | |
at 27ºC | 16.46 | |
at 40ºC | 11.76 | |
Interfacial tension at 27ºC, | IS 6104 : 1971 | 0.044 |
Flash point Pensky-Marten (closed), ºC | IS 1448 [P : 21] : 1992 | 148 |
Pour point, ºC | IS 1448 [P : 10] : 1970 | -18 |
Neutralization value | ||
a) Total acidity, | IS 1448 [P : 2] : 1967 | Nil |
b) Inorganic acidity/alkalinity | Nil | |
Corrosive sulphur | Annex B of IS 335 - 1993 | Non Corrosive |
Electric strength | 72 | |
(breakdown voltage) | IS 6792 : 1992 | |
a) New unfiltered oil, | ||
b) After filtration, min | Note 2 | |
Dielectric dissipation factor (tan δ) | IS 6262 : 1971 | 0.00025/2.05 DC |
at 90ºC, | ||
Specific resistance (resistivity) | IS 6103 : 1971 | |
a) At 90ºC, | 750 × 1012 ohm-cm | |
b) At 27ºC, | 7650 × 1012 ohm-cm | |
Oxidation stability | IS 12422 - 1988 | |
a) Neutralization value | Nil | |
after oxidation, | Nil | |
b) Total sludge, after oxidation, | ||
Oxidation stability (Rotating | IS 12958 - 1990 | 210 |
Bomb test), minutes | ||
Oxidation inhibitor, percent by, wt | IS 13631 - 1993 | 0.26 |
Water content, ppm | IS 13567 - 1992 | 9 |
If you wish to buy Transformer Oil I of HPCL from Mumbai, India then please email to sales@lubeoilcompany.com or call/whatsapp +919870666888.
Transformer Oil I, HPCL in India
We can give you the best cost prices to buy Transformer Oil I compared to all dealers, suppliers, vendors, wholesalers, retailers, traders, resellers and distributors in Mumbai, Navi Mumbai, Bhiwandi, Thane in Maharashtra and all India.
Inhibited Type Transformer Oil Transformer Oil I, HPCL in India
We can also ship Transformer Oil I to all these states of India Andhra Pradesh, Arunachal Pradesh, Assam, Bihar, Chhattisgarh, Goa, Gujarat, Haryana, Himachal Pradesh, Jharkhand, Karnataka, Kerala, Madhya Pradesh, Maharashtra, Manipur, Meghalaya, Mizoram, Nagaland, Odisha, Punjab, Rajasthan, Sikkim, Tamil Nadu, Telangana, Tripura, Uttar Pradesh, Uttarakhand, West Bengal, Andaman and Nicobar Islands, Chandigarh, Dadra and Nagar Haveli and Daman and Diu, Delhi, Jammu and Kashmir, Ladakh, Lakshadweep and Puducherry.